Thermal Imaging August 2026 11 min read

What Is Emissivity and Why Does It Matter in Electrical Thermal Inspections?

Emissivity is the single most common source of measurement error in infrared inspections. Learn what it is, how to set it, and how to avoid the mistakes that produce false temperature readings on electrical equipment.

What Is Emissivity? A Simple Definition

Emissivity is a material property that describes how efficiently a surface emits infrared radiation compared to a perfect blackbody. It is measured on a scale from 0 to 1. A perfect blackbody has an emissivity of 1.0, meaning it emits 100% of the radiation theoretically possible at its temperature. Most real materials emit less.

This matters because a thermal camera does not measure temperature directly. It measures the infrared radiation arriving at its detector and converts that radiation into a temperature reading using the emissivity value you have set. If the emissivity setting does not match the surface being inspected, the camera calculates the wrong temperature — sometimes off by tens of degrees.

For electrical inspections, the practical rule is simple: shiny metal surfaces reflect infrared and have low emissivity (0.05-0.35); painted, oxidized, or insulated surfaces emit well and have high emissivity (0.85-0.95). The EasIR handheld thermal camera makes it easy to adjust emissivity per target, which is exactly what you need when walking a switchgear room where every component has a different finish.

"Over 80% of the thermal anomalies we investigated turned out to be emissivity errors, not real faults. Once our team learned to set emissivity correctly, our false-positive rate dropped dramatically." — Electrical Maintenance Manager, Peruvian Utility

Why Emissivity Matters for Electrical Inspections

Electrical equipment is a worst-case environment for emissivity errors because it contains both extremes: bare copper and aluminum busbars with emissivity around 0.05-0.30, and painted enclosures or cable insulation with emissivity of 0.85-0.95. Scanning them with a single emissivity setting produces wildly inaccurate comparisons.

Three practical consequences of getting emissivity wrong on electrical gear:

  • False hot spots: A shiny copper lug measured at emissivity 0.95 can appear 20-40°C hotter than it really is, because the camera misinterprets reflected radiation as emitted radiation.
  • Missed real faults: A genuine connection failure on a reflective surface measured at emissivity 0.30 while the painted enclosure next to it is measured at 0.95 produces readings that cannot be compared phase-to-phase.
  • Failed trend analysis: If emissivity settings vary between inspection rounds, your historical temperature data is meaningless — the same connection will show different temperatures for no physical reason.

Standards such as NFPA 70B and the ISO 18434 series emphasize consistent measurement conditions. Setting the correct emissivity and recording it in your inspection report is one of the cheapest, most effective ways to improve data quality.

Emissivity Values for Common Electrical Materials

Material / SurfaceTypical EmissivityMeasurement Advice
Painted enclosure (most switchgear)0.90-0.95Measure directly — reliable target
Cable insulation (XLPE, PVC, EPR)0.85-0.95Measure directly on the jacket
Oxidized copper busbar0.60-0.80Use upper range after light oxidation
Bare copper busbar / lug (polished)0.05-0.15Apply flat black tape or high-emissivity paint
Bare aluminum busbar (polished)0.05-0.10Apply tape or paint before measuring
Galvanized steel enclosure0.20-0.40Use tape target or measure painted areas
Porcelain insulator0.85-0.92Measure directly on glazed surface
Transformer tank (painted)0.90-0.95Measure directly on the tank wall

The fastest field technique for a low-emissivity target is to attach a piece of flat black electrical tape (emissivity ~0.95) and wait 2-3 minutes for it to reach thermal equilibrium, then measure the tape. The Hammer II supports per-target emissivity presets, letting you switch between painted, copper, and taped targets without leaving the inspection flow.

How to Set Emissivity on a Thermal Camera

Modern Unitech Tools cameras make emissivity adjustment a menu option that takes seconds. The correct procedure in the field:

  1. Identify the target surface. Determine whether you are measuring painted metal, bare copper, cable jacket, or a taped reference.
  2. Set the emissivity value. Use the values in the table above as a starting point, or the preset list on the camera.
  3. Use a reference when in doubt. Compare the camera reading against a known reference (contact thermometer on a taped target, or a calibrated blackbody source for lab work).
  4. Account for reflected temperature. For outdoor and substation work, the camera should also compensate for the reflected background temperature (RTC) — most cameras call this the "reflected temperature" parameter. Set it to the ambient background temperature, typically 20-25°C indoors.
  5. Record the setting. Note the emissivity used for each asset so repeat inspections are comparable.

On the PT II HD thermal camera, the large touchscreen and quick-access emissivity menu make this workflow especially fast, which matters when you are inspecting hundreds of connections in a single substation visit.

Common Emissivity Mistakes That Cause False Readings

Knowing what goes wrong is half the battle. These are the errors we see most often in electrical inspection programs:

  • Using the default emissivity everywhere. Many cameras default to 0.95. Pointing that at a polished copper busbar understates or overstates temperature depending on background reflections.
  • Measuring shiny metal directly. A bare lug's reading is mostly reflected background radiation. The camera reports a temperature, but it is the background's temperature, not the lug's.
  • Ignoring reflected temperature. Near a hot transformer or in direct sunlight, reflected radiation skews readings even on high-emissivity surfaces.
  • Comparing different surfaces phase-to-phase. Comparing a painted terminal on phase A with a bare copper terminal on phase B will always show a delta, even with no fault present.
  • Dirty or oxidized surfaces. Dirt and oxide change emissivity. Wipe the surface or use a taped reference.

The result of these mistakes is the same: maintenance teams chase phantom hot spots, or worse, they trust an incorrect cool reading and miss a developing failure.

Practical Measurement Tips for the Field

Apply these techniques to keep emissivity errors out of your thermography program:

  • Tape targets: Carry flat black PVC tape (emissivity ~0.95). Apply to bare metal connections before measuring, and leave a small piece at known-good connections for calibration comparison.
  • Angle of view: Keep the camera as perpendicular to the target as possible. Highly angled views reduce the radiation collected and distort readings, especially on reflective surfaces.
  • Distance: Emissivity is a surface property, but atmospheric absorption and spot size matter at distance. Get as close as safety permits, and ensure the spot covers only the target.
  • Use the camera's multiple measurement modes: Center spot, area box, and isotherm modes help you compare regions measured under the same emissivity.
  • Document everything: Include emissivity, reflected temperature, load condition, and distance in every report. Your future data depends on it.

"We standardized on emissivity 0.95 with tape targets for all bare-metal terminations across our 34 substations. Our annual thermography reports are finally consistent enough for year-over-year comparison." — Substation Engineer, Brazilian Utility

Recommended Unitech Tools Cameras

  • EasIR Series (384×288, 15mK NETD): the cost-effective entry point for routine panel and switchgear surveys. Per-target emissivity presets and a compact body make it ideal for daily rounds.
  • Hammer II Series (640×480, 15mK, dual FOV, laser auto focus): the professional choice for formal thermography programs. Fast focus and dual field of view speed up large substation inspections while keeping emissivity control at your fingertips.
  • PT II Series (1280×1024, TwinView DFOV): maximum detail for critical assets and forensic analysis. Use it when you need the clearest possible image of a suspicious connection.

Need a Thermal Camera for Accurate Electrical Inspections?

Contact Unitech Tools for expert guidance on selecting the right thermal camera for switchgear, transformer, and substation inspection in your facility.

WhatsApp: unitechtools Request a Quote